Two D.C. shunt generators, each with armature resistance of 0.02 ohm and field resistance of 50 ohm run in parallel and supply a total current of 1000 amperes to the load circuit. If their e.m.fs. are 270 V and 265 V, their bus bar voltage will be_____________________?

Electrical Engineering Mcqs

Two D.C. shunt generators, each with armature resistance of 0.02 ohm and field resistance of 50 ohm run in parallel and supply a total current of 1000 amperes to the load circuit. If their e.m.fs. are 270 V and 265 V, their bus bar voltage will be_____________________?

(A)  270 V

(B)  267.5 V

(C)  265 V

(D)  257.4 V